Oven Venting - Fire Deck Series |
 |
|

US Customers: Below is our
Fire Deck Venting Recommendations Page. You can
choose either the Fire Deck 6045 & 8645 or the Fire Deck 9660 & 9690.
International Customers: Click Here!
6045 &
8645 Fire Decks:
The Wood Stone Fire Decks 6045 & 8645 must be vented using a Listed
Type 1 exhaust hood constructed and installed in accordance with all
relevant Local and National Codes. Wood Stone offers exhaust hoods
especially designed for the Fire Deck by
Gaylord Industries
(view specs).
Fire Deck model numbers containing a W should be vented in accordance
with codes
concerning solid fuel appliances (NFPA
96). Due to the dangers of creosote buildup and of
sparks entering the duct, these models should be vented
separately from all other kitchen equipment or
in such a manner as is acceptable to the authority having jurisdiction.
The Wood Stone customer support staff is
available to answer any questions concerning installation
and venting of the oven; call 1-800-988-8103 for assistance and
technical support.
Solid-fuel exhaust contains creosote and other substances that
accumulate in ducting, creating a risk of
fire. The rate of accumulation will vary with respect to flue gas
temperature, wood type and moisture content. Frequent, regularly
scheduled, thorough flue cleaning is the best
way to minimize the risk of flue fires.
CREOSOTE - AND THE NEED FOR ITS REMOVAL
When wood is burned slowly, it produces tar and other organic vapors,
which combine with expelled moisture to form
creosote. The creosote vapors condense in the relatively cool oven
flue of a slow-burning fire. As a result, creosote residue
accumulates in the duct. When ignited, this
creosote makes an extremely hot fire. The duct serving this oven should
be inspected at least twice a month during the
first two months of operation, to establish rate of creosote
buildup and necessary cleaning schedule. If creosote or soot has
accumulated, it should be removed to reduce
the risk of a flue fire.
WOOD STONE RECOMMENDS THAT YOU SUBMIT YOUR VENTING PLANS TO THE
AUTHORITY HAVING JURISDICTION BEFORE PROCEEDING WITH INSTALLATION
OF ANY GAS AND/OR SOLID FUEL BURNING
APPLIANCE.
9660 & 9690 Fire Decks:
The Wood Stone Fire Decks 9660 & 9690 must be vented through a 12" ID
flue collar located on the top of the oven, above the doorway.
Fire Deck model numbers containing a W should be vented in accordance
with codes
concerning solid fuel appliances (NFPA
96). Due to the dangers of creosote buildup and of
sparks entering the duct, these models should be vented
separately from all other kitchen equipment or
in such a manner as is acceptable to the authority having jurisdiction.
The Wood Stone customer support staff is
available to answer any questions concerning installation
and venting of the oven; call 1-800-988-8103 for assistance and
technical support.
The following options are the manufacturer's
recommendations for venting the Fire Deck 9660 & 9690 ovens:
1. A Listed building heating appliance chimney,
which is also
a listed grease duct connected directly to the oven flue
collar and provided with a 450 degree F (300
degree F for 9690) power ventilator listed for restaurant
appliance exhaust. A single wall
chimney/duct connector may be used to connect the oven to a listed building
heating appliance chimney also listed as a grease
duct. The chimney/duct connector should be a minimum of 0.044"
stainless steel or 16 ga. mild steel (0.055") and must maintain
a minimum of 18" clearance to combustibles.
A static pressure of -0.1 inches water column (-0.14 for
wood burning models) is necessary at the oven flue
collar to ensure that gas temperatures do not
exceed 450 degrees Fahrenheit at the fan inlet. The
CFM required
to attain this static pressure will depend on the configuration
of your particular installation but will probably be between
800 and 1000 CFM. Wood Stone provides a port in the flue collar
of the oven for insertion of a Magnehelic gauge so the installer
can monitor the draft to ensure proper operation of the
venting system.
2. A Listed exhaust hood
or one that is constructed and installed in accordance with all relevant
local and/or national codes and connected to a 450 degree F power
ventilator listed for restaurant exhaust. Exhaust hoods for wood
burning models must be constructed and installed in accordance with NFPA
96.
WOOD STONE RECOMMENDS THAT YOU SUBMIT YOUR VENTING PLANS TO THE
AUTHORITY HAVING JURISDICTION BEFORE PROCEEDING WITH INSTALLATION
OF ANY GAS AND/OR SOLID FUEL BURNING
APPLIANCE.
Top
International Customers Note: Wood Stone ovens should be vented in accordance with pertinent national,
regional and local codes concerning such appliances; check
venting plans with the authority having
jurisdiction before proceeding with installation. |