Important rule of thumb on airflow: Combustion air intake
should always come from the same room as the oven doorway. In the
examples below the placement of the facade wall dictates that the
combustion air intake must be from the front to be in the same room as
the doorway. When the air intake from the front is blocked and air
intake is taken from another room, a reverse (negative) air flow can
occur ultimately resulting in many service issues.
Note:
These principles apply to both direct connected oven installations
(shown) and ovens installed under hoods (not shown).


Top

Diagram 2 Note:
When a decorative façade is incorporated into the installation of a Wood
Stone oven care must be taken not to allow any facading to block the
oven opening designed for intake of combustion air. Any facading must
also allow for removal of the removable service panel.
Please review Diagram
1 to see the proper oven venting setup.

Top

Diagram 3 Note: Wood Stone ovens
need no additional openings to the oven room other
than for the front intake. Additional vents do not increase air
supply but disturb the intended air flow to
the oven burners. Please review
Diagram 1 to see
the proper oven venting setup.
Top

Diagram 4 Note:
If a room containing a Wood Stone oven is open to the
building's HVAC system a pressure difference can occur between the air
inside and outside of the oven room. This can adversely affect the
proper flow of combustion air to the oven burners and proper flow of
exhaust from the burners. Please review
Diagram 5
to see the proper oven venting setup.
Top

Diagram 5 Note: To correct the negative
affect of building HVAC on combustion airflow the oven room needs to be
sequestered from the HVAC system. If the oven room is open to HVAC at
the top this opening needs to be sealed off by some air tight
construction.